1.General Introduction

Yokogawa DO402G dissolved oxygen analyzer converter is a 4 wire type with high flexibility, reliability and low maintenance, accepts inputs from both galvanic and polar graphic sensors. Percent saturation, mg oxygen/l water, and ppm DO can be displayed and transmitted. Compensation for atmospheric pressure altitude, salinity and temperature are included for the best accuracy of measurement.

2.General Specifications

Items

Description

Input ranges

Dissolved Oxygen: 0- 50   mg/l (ppm)

Temperature : 0- 50 ºC (32- 122 ºF)

Span

DO concentration: minimum: 1 mg/l (ppm); maximum:   50 mg/l (ppm)
  % saturation : minimum: 10 %; maximum: 300 %
  Temperature : minimum: 25 ºC (77 ºF); maximum: 50 ºC (122 ºF)

Transmission signals

Two isolated outputs of 0/4-20mA DC with common   negative. Maximum load 600 Ω. Auxiliary output can   be chosen from temperature, DO, PI control, table, burn up (22mA) or burn   down (0 or 3.5mA) to signal failure

Temperature   compensation

0-50 ºC,

Sensor types: Pt100, Pt1000, PB36 ,22k NTC

Automatic or Manual temperature compensation.

Display

Custom liquid crystal display, with a main   display of 3 1/2 digits 12.5mm high.

Message display of 6 alphanumeric characters, 7   mm high.

Contact outputs

Four (4) SPDT relay contacts with LED   indicators.

Power supply

Voltage ratios (Applicable range):100 V (85 to   115 V) AC, 115 V ( 97.8 to 132.2 V) AC,    230 V (195.5 to 264.5 V) AC

Supply frequency rating (Applicable range): 50   / 60 Hz (± 5%)

Power consumption: 10 VA maximum for steady operation

Environment and   operational conditions

Ambient temperature: -10   to 55℃ (-14 to 131℉)
  Storage temperature: -30 to 70℃ (-22 to 158℉)
  Humidity: 10 to 90 % RH at 40℃ (100℉) (non-condensing)


3.Model Selection

Main Code

Suffix Codes

Description

DO402G





Dissolved Oxygen Converter

Type

-1




General

Power Supply


-1



115V +/-15% AC, 50/60 Hz


-2



230V +/-15% AC, 50/60 Hz


-5



100V +/-15% AC, 50/60 Hz

Language



-E


English



-J


Japanese




/U

Pipe and wall mounting hardware




/PM

Panel mounting hardware




/H3

Hood for sun protection(Carbon steel)




/H4

Hood for sun protection(Stainless steel)




/SCT

Stainless steel tag plate




/ANSI

1/2NPT




/AFTG

G 1/2




/X1

Epoxy baked finish

 

4.External Dimensions

01